What is behind this video

A car-plant transformer with no load can draw more current than at full load. It is not a short. Residual magnetism plus a poor closing instant can saturate the core. The current can hit eight to twelve times rated for a tenth of a second and trip protection.

It is a transient magnetizing current that appears when the unit is energized, even with no load. If residual magnetism remains and the breaker closes at an unfavorable point on the wave, the two add and saturate the core. It can reach eight to twelve times rated current for a tenth of a second, then decay.

At the instant of energization the current is set by the magnetic state of the core, not by the connected load. Residual flux plus an unfavorable closing angle saturates the steel and the magnetizing impedance collapses. That is why, with no load, the transient can clearly exceed the unit's rated operating current.

Not as a first step. Inrush can trip protection, but a trip by itself does not prove there is no fault. The video says to rule out a real fault with tests before raising settings. That avoids masking an internal problem just to ride through the transient.

The references behind what the video says are: IEEE Std 141 (coordination rule of thumb: can reach 8–12× for ~0.1 s).

This piece is animation and typography: it does not show TEVKO personnel. The figures are the ones in the script and can be checked against this page and the linked pages.

Transcript — English audio

Why does a car plant's transformer, with no load, draw more current than at full load? It's not a short.

It's the core. Shutdown left residual magnetism; reconnect at the wrong point of the wave and it adds up and saturates the core.

Like a dam that's already full: one more rain and it spills. It can hit 8 to 12 times rated current for 0.1 s.

But watch out: it can trip your protection. Before raising settings, rule out a real fault with tests.

So it's not always a fault. It's a saturated core.

Has yours tripped on energizing? Comment INRUSH and we'll tell you what to check.

The same captions ship as a WebVTT track inside the player. The spoken close invites a comment on the network where the video was posted. On this page the contact is ventas@tevko.com and the phone +52 33 2101 7241.

Questions this video answers

What is transformer inrush current?

It is a transient magnetizing current that appears when the unit is energized, even with no load. If residual magnetism remains and the breaker closes at an unfavorable point on the wave, the two add and saturate the core. It can reach eight to twelve times rated current for a tenth of a second, then decay.

Why can a transformer draw more current off-load than at full load?

At the instant of energization the current is set by the magnetic state of the core, not by the connected load. Residual flux plus an unfavorable closing angle saturates the steel and the magnetizing impedance collapses. That is why, with no load, the transient can clearly exceed the unit's rated operating current.

Should protection settings be raised if the transformer trips on energizing?

Not as a first step. Inrush can trip protection, but a trip by itself does not prove there is no fault. The video says to rule out a real fault with tests before raising settings. That avoids masking an internal problem just to ride through the transient.

Related pages

Technical content reviewed by TEVKO Technical Management · last reviewed: November 12, 2026