Dissolved gas analysis in oil (DGA)

Chromatography of the insulating oil to detect incipient faults — arcing, partial discharge and hot spots — from the gases dissolved in the oil, without de-energizing the transformer.

Oil filtering plant inside a site enclosure, operated by the crew
What the photo showsOil filtering plant inside a site enclosure, operated by the crew.

When a transformer's insulation suffers thermal or electrical stress, it decomposes the oil and paper, generating characteristic gases: hydrogen, methane, ethylene, acetylene, carbon monoxide and dioxide. Each fault type leaves a distinct gas 'signature'.

Share the nameplate data and the reason for the test; we reply with the proposed scope.

DGA extracts and quantifies those gases by laboratory chromatography. Interpretation — key gas, gas ratios and Duval triangles, per IEEE C57.104 and IEC 60599 — associates patterns with fault types: acetylene is usually associated with high-energy arcing, partial discharge predominantly with hydrogen, and ethylene with overheating. It is a probable association, not a conclusive diagnosis: a contaminated sample, prior oil treatment or gases migrating from the tap changer can alter the result. The response therefore depends on the finding: a doubtful result is confirmed by resampling; an abnormal one calls for a shorter sampling interval, a generation-rate calculation and broader electrical testing; and a critical finding — very high concentrations, accelerating generation, rising acetylene or a protection operation — may require urgent intervention, load restriction or de-energization, a decision the responsible personnel take without waiting for a second sample.

At TEVKO we don't just deliver numbers: we take the sample with a protocol that avoids contamination, interpret against asset history and gas generation rate (ppm/day), and recommend action — monitor, reduce load, schedule an internal inspection. The trend matters more than an isolated value.

What the diagnosis includes

Chromatography and key gas

Quantification of the seven fault gases, plus oxygen and nitrogen, and condition classification with the IEEE C57.104 and IEC 60599 criteria.

When it applies: Periodic predictive monitoring of the transformer.

Trend and generation rate

Comparison against history and ppm/day calculation to tell an active fault from a stable condition.

When it applies: When gases are elevated and action must be decided.

How we run the test

Sampling

Oil taken with a syringe/sealed container, no air contact, equipment in service.

Chromatography

Extraction and quantification of the dissolved gases in the lab.

Interpretation

Key gas, gas ratios and Duval triangles per IEEE C57.104 and IEC 60599, with generation rate; a doubtful result is confirmed by resampling.

Recommendation

Fault diagnosis, criticality and action plan (monitor, unload, internal inspection).

Video

Acetylene in transformer oil (DGA)

Acetylene in the oil is the signature of an arc. Per IEEE C57.104-2019, it forms in meaningful amounts only near 1000 °C. One sample is not enough.

Full transcript and technical context

Frequently asked questions — dissolved gas analysis in oil (dga)

What does dissolved gas analysis (DGA) detect?

It detects incipient faults inside the transformer from the gases dissolved in the oil: acetylene indicates high-energy arcing; hydrogen and methane, partial discharge; ethylene, severe insulation overheating. It is the most sensitive predictive test and is done without de-energizing.

How often should DGA be done on a transformer?

The schedule must be documented against the manufacturer's instructions, asset condition and trends, load, environment, history and failure consequences. Engineering must justify the program and reassess it when anomalies appear; this page does not prescribe a universal interval.

What interpretation methods do you use?

The methods of IEEE C57.104 and IEC 60599: key gas, gas ratios and Duval triangles. None is infallible alone: a gas pattern suggests a fault type but does not prove it by itself. That is why methods are combined, the generation rate is calculated and results are contrasted with the transformer's own history. Resampling helps rule out contamination, laboratory error or an outlier, but it does not replace immediate evaluation when the finding is critical.

Does the transformer need to be taken out of service?

No. The oil sample is taken with the transformer energized, following a protocol that avoids contaminating the sample with air. It is one of DGA's advantages over the electrical tests that do require an outage.

Do you always have to wait for a second sample before acting?

No. A second sample is useful when the result is doubtful: possible contamination, laboratory error or an isolated value with no other symptoms. If gases are above reference levels or rising between samples, the interval is shortened and the diagnosis broadened. And if the finding is critical — very high concentrations, accelerating generation, rising acetylene or a protection operation — the responsible personnel may restrict load or de-energize without waiting for another sample.

Dissolved gas analysis in oil (DGA) in images

Two workers at the side valve of a transformer, with a ladder against the unit
Two workers at the side valve of a transformer, with a ladder against the unit
Crane truck with IBC containers at a seaside facility
Crane truck with IBC containers at a seaside facility
Trailer-mounted oil treatment plant with its pump and filter, beside a power transformer in a substation yard
Trailer-mounted oil treatment plant with its pump and filter, beside a power transformer in a substation yard

Related tests and services

Talk to a transformer specialist

Tell us about your asset so we can define the assessment scope and prepare a tailored quote.

Get a quoteEmailEmergency