Transformer hot-spot temperature and aging
- Duration
- 30 seconds
- Language
- Spoken in English
- Captions
- English captions, switchable from the player
- Published
- Published November 12, 2026
What is behind this video
A data-center transformer gauge can read normal while the paper inside is cooking. It is not lying: it reads top oil, not the hot spot hidden in the winding. Per IEEE C57.91, above 110 °C at the hot spot, every 7 more degrees doubles paper aging. Paper does not regenerate.
No. It reads top-oil temperature, not the hot spot hidden in the winding. The instrument can show a normal value while that internal zone is already hotter. That is why the video says not to rely on the oil reading alone and to estimate the unit's hot-spot temperature.
Above 110 °C at the hot spot, every seven more degrees — a rounding of the 6.78 °C figure in the standard for thermally upgraded paper — doubles the aging of the paper. With heat and load accumulating, for example through a full summer, that aging adds up. The insulating paper does not regenerate afterward.
Because the life of the solid insulation is governed by the hottest point in the winding, not by the oil surface. A top-oil reading still in range can hide an already elevated hot spot. Estimating it shows the real aging of the paper before the damage can no longer be reversed.
The references behind what the video says are: IEEE C57.91 (above 110 °C at the hot spot, every ~7 °C doubles paper aging; the nearby exact figure is 6.78 °C for thermally upgraded paper, rounded to 7 in the video).
This piece is animation and typography: it does not show TEVKO personnel. The figures are the ones in the script and can be checked against this page and the linked pages.
Transcript — English audio
A data center transformer's gauge reads normal, while the paper inside is cooking. It's not lying.
It reads top oil, not the hot spot hidden in the winding. Like checking the kitchen to know if the pan will burn you.
Per IEEE, above 110 °C at the hot spot, every 7 °C more doubles paper aging. With heat and load all summer, it adds up.
But watch out: paper doesn't regenerate. So don't watch the oil.
Watch the hot spot. Comment HEAT and we'll tell you how to estimate it on yours.
The same captions ship as a WebVTT track inside the player. The spoken close invites a comment on the network where the video was posted. On this page the contact is ventas@tevko.com and the phone +52 33 2101 7241.
Questions this video answers
Does the transformer gauge measure the hot-spot temperature?
No. It reads top-oil temperature, not the hot spot hidden in the winding. The instrument can show a normal value while that internal zone is already hotter. That is why the video says not to rely on the oil reading alone and to estimate the unit's hot-spot temperature.
What does IEEE C57.91 say about paper aging?
Above 110 °C at the hot spot, every seven more degrees — a rounding of the 6.78 °C figure in the standard for thermally upgraded paper — doubles the aging of the paper. With heat and load accumulating, for example through a full summer, that aging adds up. The insulating paper does not regenerate afterward.
Why estimate the hot spot instead of only watching the oil?
Because the life of the solid insulation is governed by the hottest point in the winding, not by the oil surface. A top-oil reading still in range can hide an already elevated hot spot. Estimating it shows the real aging of the paper before the damage can no longer be reversed.
Related pages
Technical content reviewed by TEVKO Technical Management · last reviewed: November 12, 2026