Video
Substation thermography: when to repair immediately
- Duration
- 44 seconds
- Language
- Spoken in English
- Captions
- English captions, switchable from the player
- Published
- Published November 15, 2026
What is behind this video
A loose, dirty or corroded connection has more resistance and heats up with current. You can't see it: it works, like an extension cord heating at the plug, until it fails.
Thermography measures each connection energized and under load. The video cites the NETA severity table: if the temperature difference against an identical component under similar conditions exceeds 15 degrees, the action is to repair immediately.
Thermography needs current flowing: with no load there is no heat to see. It is scheduled during normal operation and the report records the load at the time of measurement.
This piece is animation and typography: it does not show TEVKO personnel. The figures are the ones in the script and can be checked against this page and the linked pages.
Transcript — English audio
When is a hot connection in your substation a fix-it-now item?
It's not a fun fact, it's the standard.
Loose, dirty or corroded connections have more resistance and heat up with current, and you can't see it with the naked eye.
Like an extension cord heating at the plug: it works, until it melts.
Thermography measures each connection energized and under load, and the NETA table says that if the difference against an identical component exceeds 15 degrees, it's repaired immediately.
But careful, with no load there's no heat to see: thermography is done with current flowing.
So it's not a pretty picture, it's a diagnosis.
Does your substation have thermography?
Comment THERMOGRAPHY and we'll tell you what to check.
The same captions ship as a WebVTT track inside the player. The spoken close invites a comment on the network where the video was posted. On this page the contact is ventas@tevko.com and the phone +52 33 2101 7241.
Questions this video answers
When is a hot connection repaired immediately?
Per the NETA table cited in the video, when the difference against an identical component exceeds 15 degrees.
Why does a connection heat up?
If it is loose, dirty or corroded it has more resistance and heats with current.
Can thermography be done without load?
No: with no current there is no heat to see. It is measured energized and under load.
Does TEVKO perform substation thermography?
Yes, with a report of each finding. Contact ventas@tevko.com.
Related pages
Technical content reviewed by TEVKO Technical Management · last reviewed: November 15, 2026