Video
SFRA test and winding shape
- Duration
- 32 seconds
- Language
- Spoken in English
- Captions
- English captions, switchable from the player
- Published
- Published November 12, 2026
What is behind this video
Your transformer may have passed ratio, resistance and megger and still be damaged. It is not an obvious electrical problem: it is mechanical. A short circuit can deform the winding from the inside without leaving shorts or poor insulation. SFRA injects a signal from 20 Hz to 2 MHz and records the fingerprint; if the winding moved, the peaks shift.
Yes. Those tests look at ratio, continuity and insulation. A short circuit can squeeze the winding from the inside and deform it without leaving shorts and with the insulation still in good condition. The damage, in that case, is mechanical. That is why the video says it is not enough to have passed the usual electrical tests.
The frequency response of the transformer. The test injects a signal from 20 hertz to 2 megahertz and records the unit's fingerprint. If the winding moved, the peaks in that fingerprint shift. The comparison is not against a single nameplate value, but against the shape the asset itself had as a reference.
Against the fingerprint of the same transformer, or against an equivalent reference. The video puts it this way: it is not whether the unit passed the tests, it is whether it still has the same shape. A shift in the peaks means the winding or the core is no longer in the geometry that had been recorded.
The references behind what the video says are: Figure from the script: SFRA injects a signal from 20 Hz to 2 MHz and records the transformer fingerprint; TEVKO technical page for the test.
This piece is animation and typography: it does not show TEVKO personnel. The figures are the ones in the script and can be checked against this page and the linked pages.
Transcript — English audio
Your transformer passed ratio, resistance and megger… and it can still be damaged.
It's not electrical, it's mechanical. A short circuit squeezes the winding from the inside and deforms it, but it still has no shorts and good insulation.
Like a cracked bell: it looks the same, but it no longer sounds the same. SFRA injects a signal from 20 hertz to 2 megahertz and records its fingerprint.
If the winding moved, the peaks shift. So it's not whether it passed the tests, it's whether it still has the same shape.
Did you know? Tell me in the comments.
The same captions ship as a WebVTT track inside the player. The spoken close invites a comment on the network where the video was posted. On this page the contact is ventas@tevko.com and the phone +52 33 2101 7241.
Questions this video answers
Can a transformer pass TTR, resistance and megger and still be damaged?
Yes. Those tests look at ratio, continuity and insulation. A short circuit can squeeze the winding from the inside and deform it without leaving shorts and with the insulation still in good condition. The damage, in that case, is mechanical. That is why the video says it is not enough to have passed the usual electrical tests.
What does an SFRA test measure?
The frequency response of the transformer. The test injects a signal from 20 hertz to 2 megahertz and records the unit's fingerprint. If the winding moved, the peaks in that fingerprint shift. The comparison is not against a single nameplate value, but against the shape the asset itself had as a reference.
What is the SFRA result compared against?
Against the fingerprint of the same transformer, or against an equivalent reference. The video puts it this way: it is not whether the unit passed the tests, it is whether it still has the same shape. A shift in the peaks means the winding or the core is no longer in the geometry that had been recorded.
Related pages
Technical content reviewed by TEVKO Technical Management · last reviewed: November 12, 2026
Request a technical assessment
Write to our sales inbox with the following and we will tell you what the next step is:
- The nameplate: rating, voltage, make and serial number.
- The location of the installation.
- The problem the unit presents, or the event that occurred.