TEVKO, transformadores y subestaciones de potencia
Trailer-mounted oil treatment plant with its pump and filter, beside a power transformer in a substation yard

Service

Dielectric oil filtering

Vacuum dehydration and filtering of transformer dielectric oil to restore dielectric strength and remove moisture, gases and particles.

Trailer-mounted oil treatment plant with its pump and filter, beside a power transformer in a substation yard
What the photo showsTrailer-mounted oil treatment plant with its pump and filter, beside a power transformer in a substation yard.

The dielectric oil is the transformer's insulation and coolant. Moisture and particles lower its dielectric strength and accelerate insulation ageing; filtering restores those properties without changing the oil's base chemistry.

Share the nameplate data and the condition you observe; we reply with the proposed scope.

Vacuum thermo-dehydration heats the oil and exposes it to vacuum, extracting water and gases, while filters remove solid particles. It is the right option when the physicochemical analysis shows a sound but contaminated oil. The treatment is decided and verified with before-and-after oil analysis — dielectric strength, moisture, physicochemical parameters and DGA — with the laboratory tests run at a specialized laboratory on samples taken on site.

Filtering and degassing do not correct oxidation: acidity and interfacial tension only improve with regeneration, or are resolved by replacing the oil. When the oil is chemically degraded, regeneration or replacement is the right path instead — the decision always comes from the oil analysis, not from age.

What we treat

Vacuum thermo-dehydration

Removal of moisture and dissolved gases from the oil under vacuum; restores dielectric strength and low water content but does not correct acidity or interfacial tension.

When it applies: Oil with high moisture but sound chemistry.

Particle filtering

Removal of solid contaminants to restore dielectric strength.

When it applies: Oil contaminated with particles.

How we execute the service

Analysis

Physicochemical analysis to confirm filtering is the right option.

Treatment

Vacuum thermo-dehydration and particle filtering.

Verification

Dielectric strength and moisture re-tested.

Protocol

Documented before/after report.

Frequently asked questions — dielectric oil filtering

What does dielectric oil filtering do?

It removes moisture, dissolved gases and particles by vacuum thermo-dehydration, restoring the oil's dielectric strength when the oil is sound but contaminated.

When is filtering enough vs. regeneration?

Filtering suits a chemically sound but contaminated oil. If acidity is high (oxidation products), regeneration or replacement is needed. The oil analysis decides.

Can it be done in service?

In some cases filtering can be done with the transformer energized; in others an outage is preferred. We define it per asset and scope.

Does filtering remove moisture from the paper?

It mainly treats the oil; deep moisture lives in the paper. Severe cases require drying of the solid insulation, not just oil filtering.

What is the difference between filtering, degassing, regenerating and replacing the oil?

Filtering removes particles and part of the water. Degassing, under vacuum and usually with heating (thermo-vacuum), extracts dissolved gases and moisture. Conditioning combines both. None of these processes corrects oxidation: regeneration, with adsorbent media, reduces acidity and oxidation products, and replacement substitutes the fluid. The physicochemical analysis indicates which one applies. Degassing also removes the gases that DGA reads, so after treatment the gas history restarts its baseline.

Dielectric oil filtering in images

Technician adjusting a valve on a trailer-mounted oil treatment plant, with the filter vessel and its panel in view
Technician adjusting a valve on a trailer-mounted oil treatment plant, with the filter vessel and its panel in view
Blue trailer-mounted oil treatment plant with its filter columns and pump in view
Blue trailer-mounted oil treatment plant with its filter columns and pump in view
Oil treatment pumps and vessels set up beside a power transformer, with the technician standing alongside
Oil treatment pumps and vessels set up beside a power transformer, with the technician standing alongside
Stream of insulating oil entering the mouth of a vessel, guided by a technician holding the hose over the cover
Stream of insulating oil entering the mouth of a vessel, guided by a technician holding the hose over the cover
Truck with IBC containers and oil treatment equipment in the yard of an industrial facility
Truck with IBC containers and oil treatment equipment in the yard of an industrial facility

Related services

Talk to a transformer specialist

Tell us about your asset so we can define the assessment scope and prepare a tailored quote.

Get a quoteEmailEmergency